Motor Fails to Start

Illustrated checks and practical tips for finding the cause.

Updated November 22, 2026 · Free online reference

Follow the troubleshooting steps

Motor will not start? Follow interactive checks for missing voltage, single phasing, low voltage, wiring, overloads, capacitors and brushes.

Tap or click a fault check for troubleshooting steps, a visual guide and a practical tip. If that cause is not confirmed, follow the false path to the next check. The true arrow points to the fault check to open. Several faults can exist together; the order is a suggested sequence, rather than a universal ranking of how often faults occur.

Before inspection: isolate all energy sources, follow lockout/tagout and verify absence of voltage. Control stored electrical and mechanical energy. Energized measurements are for qualified electrical personnel using the site’s approved procedure and correctly rated equipment. Use the motor and machine manuals for specific limits and repairs.

  1. No voltage supplyTap/Click if this fault is seen
  2. Single phasing at the starterTap/Click if this fault is seen
  3. Low voltage supplyTap/Click if this fault is seen
  4. Wrong control connectionsTap/Click if this fault is seen
  5. Loose connectionTap/Click if this fault is seen
  6. OverloadTap/Click if this fault is seen
  7. Bad capacitor (single phase)Tap/Click if this fault is seen
  8. BrushesTap/Click if this fault is seen

No voltage supply

Possible cause 1 of 8 · Motor Fails to Start

AI-generated reference: No voltage supply. Arrow: the open disconnect contact. Trace the supply path; a photo cannot establish absence of voltage.
AI-generated reference. Arrow: the open disconnect contact. Trace the supply path; a photo cannot establish absence of voltage. View full size.

First establish where power stops reaching the motor. A silent starter, an unenergized coil and a closed contactor with no motor output point to different parts of the circuit.

Safe approach: Isolate and verify before access or resistance tests. Any necessary live measurements require qualified personnel and the approved procedure.

Checks and troubleshooting steps

  1. Confirm the symptom: note whether the starter pulls in, the motor hums, or the overload indicates a trip. Read the machine schematic and identify all power and control supplies.
  2. A qualified electrical worker can compare the incoming supply, starter output and motor terminal voltage using correctly rated instruments and the approved energized-testing procedure. Check all phase-to-phase pairs on a three-phase supply.
  3. If the contactor does not pull in, trace the control circuit through its fuse, stop circuit, overload contact, permissives and start command. A missing PLC output may reflect an unsatisfied permissive; do not bypass it.
  4. Isolate, lock out and verify absence of voltage before repairing connections or testing continuity. Find the cause of a blown fuse or tripped overload before restoring service.
Motor starter power terminals and associated circuit diagram
Motor starter power terminals and associated circuit diagram. View full size.

Diagnostic tip: A closed contactor does not prove that power reaches the motor. Compare evidence on both sides of the starter, rather than replacing the motor first.

Additional visual reference

No voltage supply: trace supply → starter → motor; check the control command separately
Supplemental concept illustration for No voltage supply. View full size.
Full work method and return-to-service precautions

Isolate, lock out and verify before access, adjustment or resistance testing. Control stored electrical and mechanical energy. Any necessary live measurements require qualified personnel, correctly rated equipment and the approved energized-testing procedure. Restore guards and covers before a running check.

After correcting a confirmed fault, document the findings and verify operation under the equipment’s approved return-to-service procedure. If the cause remains uncertain, use the manufacturer’s service support or a qualified motor repair specialist.

Single phasing at the starter

Possible cause 2 of 8 · Motor Fails to Start

AI-generated reference: Single phasing. Arrow: a damaged starter contact that can interrupt one phase. Verify all supply paths.
AI-generated reference. Arrow: a damaged starter contact that can interrupt one phase. Verify all supply paths. View full size.

A missing phase can prevent starting or let a running motor overheat. Check each supply path; apparent voltage on an open phase can be misleading because of motor backfeed.

Safe approach: Isolate and verify before access or resistance tests. Any necessary live measurements require qualified personnel and the approved procedure.

Checks and troubleshooting steps

  1. Check the trip history and identify the three supply phases on the drawing. A blown fuse, damaged contactor pole or loose termination can interrupt one phase.
  2. Under an approved energized-testing procedure, a qualified worker measures L1–L2, L2–L3 and L3–L1 at the supply and load sides of the starter. Motor backfeed can make an open phase appear to have voltage; interpret voltage together with phase-current readings.
  3. Lock out all sources, prove the circuit dead, and isolate components as required. Test each fuse and contactor path for continuity; inspect for heat damage. Never use resistance mode on an energized circuit.
  4. If the fault remains, disconnect the motor and cable as the manufacturer directs so each can be tested separately. Compare winding resistance and use a suitable insulation-resistance test when indicated; a basic ohmmeter cannot establish insulation health.
Three-phase motor starter terminals
Three-phase motor starter terminals. View full size.
Lock and tag used to isolate equipment
Lock and tag used to isolate equipment. View full size.
Motor winding test illustration; test method depends on winding connection
Motor winding test illustration; test method depends on winding connection. View full size.

Diagnostic tip: A running three-phase motor may continue on two phases while overheating. Stop it promptly and repair the missing phase; repeated starts can damage the windings.

Additional visual reference

Single phasing at the starter: one interrupted supply path; compare phase current as well as voltage
Supplemental concept illustration for Single phasing at the starter. View full size.
Full work method and return-to-service precautions

Isolate, lock out and verify before access, adjustment or resistance testing. Control stored electrical and mechanical energy. Any necessary live measurements require qualified personnel, correctly rated equipment and the approved energized-testing procedure. Restore guards and covers before a running check.

After correcting a confirmed fault, document the findings and verify operation under the equipment’s approved return-to-service procedure. If the cause remains uncertain, use the manufacturer’s service support or a qualified motor repair specialist.

Low voltage supply

Possible cause 3 of 8 · Motor Fails to Start

AI-generated reference: Low voltage supply. Arrow: voltage-monitoring inputs. Low voltage must be established by suitable measurements.
AI-generated reference. Arrow: voltage-monitoring inputs. Low voltage must be established by suitable measurements. View full size.

The supply may look acceptable before starting yet sag during acceleration. Compare measurements at the motor with its actual nameplate rating and permitted operating range.

Safe approach: Isolate and verify before access or resistance tests. Any necessary live measurements require qualified personnel and the approved procedure.

Checks and troubleshooting steps

  1. Read the motor nameplate voltage, frequency and connection diagram. Compare the supply with the motor rating, not just the nominal distribution-system voltage.
  2. A qualified worker records all three phase-to-phase voltages at the motor during the relevant operating condition using the site’s energized-testing procedure. Starting voltage drop may need a recording instrument.
  3. Compare the readings with the motor manufacturer’s permitted operating range. Check supply loading, cable length and size, transformer taps and starter contacts when voltage drops excessively.
  4. Lock out before correcting terminations or changing connections. After repairs, verify voltage balance, acceleration and current with covers and guards restored.
Examples of low-voltage industrial motors
Examples of low-voltage industrial motors. View full size.
Example three-phase voltage relationships; use the actual supply and motor ratings
Example three-phase voltage relationships; use the actual supply and motor ratings. View full size.

Diagnostic tip: An acceptable average voltage can hide a badly unbalanced supply. Do not assume that a 480 V supply means the motor nameplate also says 480 V.

Additional visual reference

Low voltage supply: look for voltage drop during starting; compare all phase-to-phase readings
Supplemental concept illustration for Low voltage supply. View full size.
Full work method and return-to-service precautions

Isolate, lock out and verify before access, adjustment or resistance testing. Control stored electrical and mechanical energy. Any necessary live measurements require qualified personnel, correctly rated equipment and the approved energized-testing procedure. Restore guards and covers before a running check.

After correcting a confirmed fault, document the findings and verify operation under the equipment’s approved return-to-service procedure. If the cause remains uncertain, use the manufacturer’s service support or a qualified motor repair specialist.

Wrong control connections

Possible cause 4 of 8 · Motor Fails to Start

AI-generated reference: Wrong motor connections. Arrow: terminal links to compare with this motor’s exact wiring diagram. The arrangement shown is illustrative.
AI-generated reference. Arrow: terminal links to compare with this motor’s exact wiring diagram. The arrangement shown is illustrative. View full size.

Suspect the connection arrangement when trouble starts after rewiring or motor replacement. Verify lead numbers, links and control wiring against the exact motor and machine diagrams.

Safe approach: Isolate and verify before access or resistance tests. Any necessary live measurements require qualified personnel and the approved procedure.

Checks and troubleshooting steps

  1. With all sources isolated and absence of voltage verified, compare every motor lead and link with the specific nameplate connection diagram. Photograph and label the original wiring before disturbing it.
  2. Check the selected connection against the actual supply voltage. Dual-voltage and wye/delta arrangements differ by motor design; matching wire colors alone is insufficient.
  3. Compare the starter control wiring with the machine schematic, including coil voltage, overload auxiliary contact and permissives. Restore missing protective-earth bonds to the specified bonding point.
  4. Check terminal condition, clearances and manufacturer-specified torque. Restore covers, then have qualified personnel verify rotation and current using the machine’s controlled commissioning procedure.
How to read the ratings and connection information on a motor nameplate
How to read the ratings and connection information on a motor nameplate. View full size.
Corroded motor terminals showing the importance of visual inspection
Corroded motor terminals showing the importance of visual inspection. View full size.

Diagnostic tip: An ordinary continuity check is useful for finding an open bond, but it does not by itself prove a compliant protective-earth fault path. Never use an arbitrary earth rod as the only reference.

Additional visual reference

Wrong control connections: check lead numbers and link positions; match the connection to the actual supply
Supplemental concept illustration for Wrong control connections. View full size.
Full work method and return-to-service precautions

Isolate, lock out and verify before access, adjustment or resistance testing. Control stored electrical and mechanical energy. Any necessary live measurements require qualified personnel, correctly rated equipment and the approved energized-testing procedure. Restore guards and covers before a running check.

After correcting a confirmed fault, document the findings and verify operation under the equipment’s approved return-to-service procedure. If the cause remains uncertain, use the manufacturer’s service support or a qualified motor repair specialist.

Loose connection at some terminal lug

Possible cause 5 of 8 · Motor Fails to Start

AI-generated reference: Loose or heat-damaged connection. Arrow: the poorly seated lug. Inspect heat damage and use the specified repair and torque procedure.
AI-generated reference. Arrow: the poorly seated lug. Inspect heat damage and use the specified repair and torque procedure. View full size.

A loose or damaged termination can interrupt starting power and create local heating. Find the affected connection and assess heat damage before tightening or returning it to service.

Safe approach: Isolate and verify before access or resistance tests. Any necessary live measurements require qualified personnel and the approved procedure.

Checks and troubleshooting steps

  1. Lock out power and any separate control feeds; verify absence of voltage before opening terminal boxes.
  2. Inspect starter poles, overload terminals, junctions and motor lugs for discoloration, melted insulation, corrosion or broken strands.
  3. Replace heat-damaged lugs or conductors and tighten serviceable terminals to the equipment maker’s torque specification with the correct tool. Do not simply overtighten every screw.
  4. Restore barriers and covers, then verify normal starting and balanced phase currents. A qualified worker can use a thermal survey under load to confirm the repair.

Diagnostic tip: Heat damage can extend beneath insulation. Tightening a burnt terminal without replacing damaged parts often leaves the fault in place.

Additional visual reference

Loose connection at some terminal lug: inspect the lug and conductor together; use the specified terminal torque
Supplemental concept illustration for Loose connection at some terminal lug. View full size.
Full work method and return-to-service precautions

Isolate, lock out and verify before access, adjustment or resistance testing. Control stored electrical and mechanical energy. Any necessary live measurements require qualified personnel, correctly rated equipment and the approved energized-testing procedure. Restore guards and covers before a running check.

After correcting a confirmed fault, document the findings and verify operation under the equipment’s approved return-to-service procedure. If the cause remains uncertain, use the manufacturer’s service support or a qualified motor repair specialist.

Overload

Possible cause 6 of 8 · Motor Fails to Start

AI-generated reference: Motor overload assessment. Arrow: clamp around one phase conductor. Overload requires current, load and duty checks; no reading is implied here.
AI-generated reference. Arrow: clamp around one phase conductor. Overload requires current, load and duty checks; no reading is implied here. View full size.

A trip or stalled start can originate in the driven machine, the supply or the protection setting. Use the trip history and load condition to separate those possibilities.

Safe approach: Lock out all energy sources and secure moving parts before hands-on checks. Restore guards before running tests.

Checks and troubleshooting steps

  1. Record the overload indication, trip time and recent changes in product, belt tension or driven equipment. Avoid repeated resets.
  2. Lock out and secure the machine against stored energy or movement. Inspect the driven equipment for jamming, seized bearings or an applied brake.
  3. Compare the overload device, trip class and setting with the motor nameplate and manufacturer’s instructions. A qualified worker checks phase currents and supply balance during an approved test.
  4. If the machine permits a decoupled test, have qualified personnel safely uncouple, secure keys and restore guarding before a controlled run. A successful unloaded run points toward the load; it does not rule out every motor fault.

Diagnostic tip: An overload trip is evidence, not a diagnosis. Do not increase the setting to keep the motor running without resolving the cause.

Additional visual reference

Overload: inspect the driven load for binding; investigate the trip before resetting
Supplemental concept illustration for Overload. View full size.
Full work method and return-to-service precautions

Isolate, lock out and verify before access, adjustment or resistance testing. Control stored electrical and mechanical energy. Any necessary live measurements require qualified personnel, correctly rated equipment and the approved energized-testing procedure. Restore guards and covers before a running check.

After correcting a confirmed fault, document the findings and verify operation under the equipment’s approved return-to-service procedure. If the cause remains uncertain, use the manufacturer’s service support or a qualified motor repair specialist.

Bad capacitor (single phase motor)

Possible cause 7 of 8 · Motor Fails to Start

AI-generated reference: Failed motor capacitor. Arrow: a swollen or lifted end seal. Visible damage is one clue; verify capacitor type and condition safely.
AI-generated reference. Arrow: a swollen or lifted end seal. Visible damage is one clue; verify capacitor type and condition safely. View full size.

On a motor that uses capacitors, a failed start or run capacitor can prevent acceleration. Confirm the capacitor type and check the starting device too; a hum alone does not identify the cause.

Safe approach: Isolate, lock out and verify absence of voltage. Follow the specified capacitor discharge procedure before handling.

Checks and troubleshooting steps

  1. Confirm from the motor diagram that a start or run capacitor is used. A hum with no acceleration can also indicate a jam, low voltage or a failed starting switch.
  2. Isolate, lock out and verify the circuit dead. Treat the capacitor as stored energy; discharge it by the manufacturer’s specified method and verify safe voltage before touching terminals.
  3. Isolate the capacitor from the circuit and inspect for swelling, leakage or damaged terminals. Qualified personnel compare capacitance with the marked value and tolerance using the correct tester.
  4. Use the manufacturer-specified capacitor type, capacitance and voltage rating. Check the start switch or relay and restore covers before a controlled start.

Diagnostic tip: Never short capacitor terminals with a screwdriver, and do not substitute a run capacitor for a start capacitor just because it fits.

Additional visual reference

Bad capacitor (single phase motor): confirm start or run capacitor type; control and verify stored energy first
Supplemental concept illustration for Bad capacitor (single phase motor). View full size.
Full work method and return-to-service precautions

Isolate, lock out and verify before access, adjustment or resistance testing. Control stored electrical and mechanical energy. Any necessary live measurements require qualified personnel, correctly rated equipment and the approved energized-testing procedure. Restore guards and covers before a running check.

After correcting a confirmed fault, document the findings and verify operation under the equipment’s approved return-to-service procedure. If the cause remains uncertain, use the manufacturer’s service support or a qualified motor repair specialist.

Brushes

Possible cause 8 of 8 · Motor Fails to Start

AI-generated reference: Worn carbon brushes. Arrow: the shortened carbon brush. Compare remaining length with the motor manufacturer’s limit.
AI-generated reference. Arrow: the shortened carbon brush. Compare remaining length with the motor manufacturer’s limit. View full size.

Worn or stuck brushes can interrupt contact on motors that use them. Identify the brush arrangement before checking wear, movement, springs and the ring or commutator surface.

Safe approach: Lock out all energy sources and secure moving parts before hands-on checks. Restore guards before running tests.

Checks and troubleshooting steps

  1. Confirm that the motor actually has brushes; most squirrel-cage induction motors do not. Identify whether the surface is a commutator or slip ring.
  2. With power isolated, stored energy controlled and the rotor stopped, inspect brush wear, leads, springs and holders.
  3. Check that the specified brush grade slides freely and makes the manufacturer-required contact. Clean carbon dust by the approved method and replace worn or damaged brushes as specified.
  4. Inspect the ring or commutator surface and follow the maker’s seating and commissioning procedure. Refit guards before any running assessment.

Diagnostic tip: Correct brush grade and spring pressure matter as much as brush length. Mixing grades can cause unequal current sharing.

Additional visual reference

Brushes: check remaining brush length and contact; inspect the holder, spring and flexible lead
Supplemental concept illustration for Brushes. View full size.
Full work method and return-to-service precautions

Isolate, lock out and verify before access, adjustment or resistance testing. Control stored electrical and mechanical energy. Any necessary live measurements require qualified personnel, correctly rated equipment and the approved energized-testing procedure. Restore guards and covers before a running check.

After correcting a confirmed fault, document the findings and verify operation under the equipment’s approved return-to-service procedure. If the cause remains uncertain, use the manufacturer’s service support or a qualified motor repair specialist.

End of this checking sequence.

Visual reference

Frequently asked questions

How do I investigate Motor Fails to Start?

Start with the first applicable fault check and compare its checks with the machine’s actual symptoms. If the cause is not confirmed, move to the next fault check. More than one fault can be present; verify the repair at normal load and speed.

Can I use every check on any motor?

Choose only the checks that apply to the motor design and equipment. Electrical testing and repairs require qualified personnel and the site’s approved procedures. Manufacturer-specific ratings, clearances, lubrication and wiring take precedence.

Source references and further learning

This general guide helps organize fault finding. Manufacturer manuals determine the correct tests, tolerances, lubricant quantities and repair methods for the actual motor.