What you’ll learn
- Alternate lead compressors
- Add lag capacity on demand
- Evaluate runtime and cycling
Recommended prerequisite: Timers and relay logic
Practice lead/lag control of two simulated air compressors. These settings are for the virtual lab, not a design specification for physical equipment.
1. Single compressor
- Select the dual compressor simulation. Set PE1 (I:1/02) to 120 psi with a 20 psi span and discharge flow to 50%.
- Use the panel start/stop controls to enable the system and command compressor 1 (O:2/0). Indicate system enable with Run and actual compressor operation with C1.
- Download and run. Verify cutout at 120 psi and restart below 100 psi.
2. Alternate the lead compressor
- Retain the PE1 settings and alternate the selected compressor after each completed pressure recovery using basic relay instructions.
- Test at 50%, then 80% and 100% flow; observe when one compressor cannot recover pressure.
3. Add lag capacity
- Use PE2 to call the idle compressor at 98 psi; keep both operating until full pressure is restored.
- Verify alternation at 50% flow and joint operation under heavy demand. Compare behavior at 78%, 80% and 82% flow.
4. Improve the control strategy
- Develop a timing or demand-estimation strategy to avoid prolonged single-compressor operation while limiting short cycling.
- Retain low-pressure assistance and light-load alternation; tune the simulated settings and compare accumulated runtime for each unit using the selector and LEDs.
Exercise basis: Professor Bill’s LadderLab, Dual Compressor student exercises (Canadu). See the help index for supplier information.
Lesson FAQs
How do I alternate two compressors?
Change the lead selection once per completed demand cycle, not every PLC scan.
Why can one compressor run continuously?
Demand can approach its capacity without triggering the low-pressure lag switch. Test a runtime-based assistance strategy and check for short cycling.